Page 38 of 40 FIRElink-100 – Installation Manual
© 2010 Hochiki Europe (UK) Ltd
9-5-0-345/ISS4/OCT10
protected area to ensure normal flow. This will require the detector to be installed using the piped
exhaust docking station (see section 3.1).
8.5.1 "Low Flow" Error Messages.
Check that the pipe giving the error is not blocked
Check that the low flow fault threshold is not set too high (see section 1.11.3)
8.5.2 "High Flow" Error Messages
Check that the pipe is pushed home into the inlet and is not broken or cracked
Check that installed pipe-work is fitted with an end-cap. The FIRElink PipeCAD® pipe modelling
software prompts the use of appropriate end-caps.
Open bore pipes are not recommended.
Check that the high flow fault threshold is not set too low (see section 1.11.2)